Legrand / Raritan / Server Technology Xerus™ JSON-RPC API
|
Public Attributes | |
| ModbusEndianness | endianness |
| Modbus 16-bit-words should be transmitted in big endian order. More... | |
Public Attributes inherited from peripheral::GatewaySensorManager::ModbusValueEncoding8 | |
| boolean | byteSwap |
| 16-bit modbus words should be transferred in big-endian byte order. More... | |
| long | mask |
| mask raw value before interpreting (0 = not masked, the same as 0xFFFF...) | |
Public Attributes inherited from peripheral::GatewaySensorManager::NumericValueEncoding | |
| float | scalingFactor |
| multiply with when interpreting as numeric value | |
| float | offset |
| add value after applying scalingFactor | |
Public Attributes inherited from peripheral::GatewaySensorManager::ValueEncoding | |
| string | encodingId |
| encoding type id | |
| EncodingType | type |
| value coding type | |
| boolean | invertState |
| invert when interpreting as state | |
| vector< InterpretationRule > | interpretationRules |
| error/value inerpretation rules | |
| ModbusEndianness peripheral::GatewaySensorManager::ModbusValueEncoding32::endianness |
Modbus 16-bit-words should be transmitted in big endian order.
For modbus devices that do not comply with this, endianness must be set to LITTLE_ENDIAN.